Silicone rubber cable YGCP
YGCP silicone rubber cable is suitable for fixed installation of power transmission lines or connecting cables for mobile appliances with AC rated voltage of 0.6/1KV and below. The product has the characteristics of heat radiation resistance, cold resistance, and corrosive gases. The cable structure is soft, easy to radiate, and the electrical performance is stable and outstanding in high temperature (cold) environments. It has a long service life and is widely used in industries such as metallurgy, power, petrochemicals, electronics, and automobile manufacturing·
Product Usage Editing
This product is suitable for mobile or fixed electrical instrument connection lines or signal transmission with AC rated voltage of 450/750V and below. The cable has good thermal stability and can maintain good electrical performance and flexibility in high temperature, low temperature, and corrosive environments. It is suitable for use in industries such as metallurgy, power, and petrochemicals with requirements for mobile temperature resistance.
Implementation standard for silicone rubber power cables: Flame retardant and fire resistance characteristics test shall comply with GB12666-90 requirements:
Characteristics of using silicone rubber power cables:
1. Rated AC voltage: U0/U 0.6/1KV
Working temperature: 180 ℃
Environmental temperature: Fixed installation -60 ℃
2. The temperature for cable installation and laying should not be lower than -25 ℃.
3. Allowable bending radius for cables: The minimum bending radius for cables is 10 times the outer diameter of the cable
Basic models and names of silicone rubber power cables:
model
product name
YGC
Silicone rubber insulated and silicone rubber sheathed power cable
YGCR
Silicone rubber insulated silicone rubber sheathed mobile power flexible cable
YGCP
Silicone rubber insulated, silicone rubber sheathed, copper braided shielded power cable
YGC22
Silicone rubber insulated, silicone rubber sheathed, steel tape armored power cable
JGG
Installation line with silicone rubber insulation and silicone rubber sheath
JGGR
Silicone rubber insulation, silicone rubber sheath, mobile installation flexible wire
JGGP
Silicone rubber insulation, silicone rubber sheath, copper braided shielding installation wire
JHXG
Silicone rubber insulated motor lead wire
Note: ZR should be added before the model of flame-retardant silicone rubber cable, and tin plating can be used for the copper wire in the conductor core.
Silicone rubber power cable code name and meaning:
code
Meaning of code
Y-series code mobile flexible cable
G-Silicone rubber
C-Heavy duty
22- Steel belt armor
P-Copper Braided Shielding
R-multi stranded conductor
J-Motor lead wire
Main technical indicators of silicone rubber power cables
1. The R-class DC resistance of the finished cable conductor meets the requirements of GB3956, refer to Appendix A Table 1 and Table 2.
The insulation resistance at 2.20 ℃ shall not be less than 100M Ω/KM
3. The finished cable shall withstand an AC 50HZ3.5KV/5min voltage test without breakdown.